Pennco NATURAL GAS TO LP Manual de usuario

Busca en linea o descarga Manual de usuario para Equipo Pennco NATURAL GAS TO LP. Pennco NATURAL GAS TO LP User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 4
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
P/N 24004821, Rev. D [11/2014]
CONVERSION INSTRUCTIONS
NATURAL GAS TO LP (SEA LEVEL TO 2000 FEET)
Cast Iron Gas Fired Water Boilers
15B, BWB, UH15B, GMGWB
For Forced Hot Water
WARNING
This conversion kit shall be installed by a qualied
service agency in accordance with the manufacturer’s
instructions and all applicable codes and requirements
of the authority having jurisdiction. If the information
in these instructions is not followed exactly, a re,
an explosion or production of carbon monoxide may
result causing property damage, personal injury or
loss of life. The qualied service agency is responsible
for the proper installation of this kit. The installation
is not proper and complete until the operation of the
converted appliance is checked as specied in the
manufacturer’s instructions supplied with the kit.
!
KIT CONTENTS
ITEM QTY.
Installation Instructions 1
Conversion Plate/Label 1
Pilot Orice - Spark 1
Pilot Orice - 24 Volt 1
Liquid Sealing Compound 1
Spring Kit 1
Tools Required
Flat Head Screwdriver, 1/4” Nut Driver, 7/16” Open Ended
Wrench, 3/16” Allen Wrench, 18” Manometer (or dial
manometer)
Installation
1.
Turn off gas supply to the boiler.
WARNING
Electrical shock hazard. Turn OFF electrical power
supply at service panel before making electrical
connections. Failure to do so could result in death
or serious injury.
!
2.
Turn off all electrical to boiler.
3.
Remove front panel.
4.
Remove burner access door.
5.
Remove main gas burner tubes. See Figure 1.
6.
Remove main burner orices. See Figure 1.
7.
Install supplied LP gas main burner orices. See Table3
for orice size and quantities.
8.
Use 7/16” wrench, disconnect pilot tube from pilot. See
Figure 2.
9.
Remove pilot orice. See Figure 2.
10.
Install LP gas pilot orice. See Figure 2.
11.
Apply liquid sealing compound to threads of pilot
assembly tting.
12.
Attach pilot tube to pilot and securely tighten. See
Figure 2.
13.
Replace main gas burner tubes.
14.
Remove the cover screw from gas valve pressure
regulator. See Figure 4.
PILOT ORIFICES
MFG. PART NUMBER
Honeywell 390686-36*
*Use 390686-40 for Boilers Manufactured before July
2008 with Q381 Pilot.
GAS VALVE
KNOB
ORIFICES
BURNERS
Figure 1
Figure 2
Pilot Orice
Pilot
Pilot Tube
Vista de pagina 0
1 2 3 4

Indice de contenidos

Pagina 1 - For Forced Hot Water

P/N 24004821, Rev. D [11/2014]CONVERSION INSTRUCTIONSNATURAL GAS TO LP (SEA LEVEL TO 2000 FEET)Cast Iron Gas Fired Water Boilers 15B, BWB, UH15B, GMGW

Pagina 2

2NATURAL GAS TO LP CONVERSION INSTRUCTIONSFigure 3 - Gas Valve15. Remove adjustment screw by turning counterclockwise . See Figure 4.16. Remove stainl

Pagina 3 - Figure 6 - Burner with Mantel

3Figure 4 - Gas ValveNATURAL GAS TO LP CONVERSION INSTRUCTIONS• Thermostat actuates on call for heat, completing circuit to control. • Completed circu

Pagina 4 - Ignition

NATURAL GAS TO LP CONVERSION INSTRUCTIONSFigure 7 - Pilot3/8” To 1/2” In FlameIgnition Electrode

Comentarios a estos manuales